Manual Adjustment Procedure
1. At the [Site Setup Data] Menu, press the <Right Arrow> key and scroll to the [HF] menu
2. Press the <Right Arrow> key and use the keypad keys to input the desired correction
3. The new correction value will appear in the [HF] menu cell as shown below.
Automatic Adjustment Procedure
1. At the [Site Setup Data] Menu, press the <<Right Arrow> key and scroll to the [HF] menu
2. Press the <Right Arrow> key and [Manual] will appear.
3. Press the <Up or Down Arrow> keys to select [Automatic] then press <ENTER>.
FST020 IP65 NEMA 4X
Operating Instructions, 02/2012, A5E03086487-05
cell. Press the <Right Arrow> key and [Manual] will appear in the display.
value. Press <ENTER> to input value.
cell.
Troubleshooting
10.4 Site Setup Data
115