Decommissioning And Removal; Decommissioning; Removing The Differential Pressure Meter; Disposal - Samson Media 7 Mounting And Operating Instructions

Differential pressure meter with remote data transmission
Table of Contents

Advertisement

11 Decommissioning and
removal

11.1 Decommissioning

To decommission the differential pressure
meter before removing it, proceed as fol-
lows:
1. Isolate measuring lines.
Î When a valve block is used:
2. Close the shut-off valves.
3. Open the equalizing valve.
4. Slowly open the screw of the test con-
nection to release the pressure.
5. Disconnect the power supply.
6. Open the housing cover of the differen-
tial pressure meter and disconnect the
wires for the power supply.
11.2 Removing the differential
pressure meter
1. Disconnect the wires for the power sup-
ply from the differential pressure meter.
2. To remove the differential pressure meter,
loosen the fastening screws on the de-
vice.
EB 9510 EN

Decommissioning and removal

11.3 Disposal

Î Do not dispose of components, lubricants
and hazardous substances together with
your other household waste.
Î Check whether a battery is inserted in
the differential pressure meter and re-
move it before disposing of the device.
Î Observe local, national and internation-
al refuse regulations before disposing of
the device and its batteries.
Note
We can provide you with a recycling
passport according to PAS 1049
on request. Simply e-mail us at
aftersalesservice@samsongroup.com giving
details of your company address.
Tip
On request, we can appoint a service
provider to dismantle and recycle the
product.
71