Connecting The Wiring - Samson Media 7 Mounting And Operating Instructions

Differential pressure meter with remote data transmission
Table of Contents

Advertisement

Mounting and start-up
5.4.2

Connecting the wiring

Î Connect the wiring as shown in Fig. 7.
Î Insert the wire without force.
Î To remove the wire, use a slotted screw-
driver to press the unlocking slot of the
cage clamp terminal and remove the
wire.
Î Route the grounding connection (PE) to
the corresponding terminal.
NOTICE
!
Risk of malfunction due to incorrect power
line frequency setting.
The local power line frequency must be en-
tered to be able to properly filter out any dis-
turbances which are transmitted over ground
wires or external power supply units.
The power line frequency (50/60 Hz) is en-
tered in menu item 1.10 (see page 74).
The procedure to enter or change the param-
eters is described in section 7 on page 52
onwards.
36
EB 9510 EN