Performing Zero Calibration - Samson Media 7 Mounting And Operating Instructions

Differential pressure meter with remote data transmission
Table of Contents

Advertisement

1. Press
key (in start screen) to go to the main menu.
2. Select Start-up (1) with
3. Select User level (1.1) with
4. Press
key and select 'Specialist' with
5. Press
key to confirm the setting.
Activating password protection
The password can only be changed and activated in the Specialist user level.
1. Press
key (in start screen) to go to the main menu.
2. Select Start-up (1) with
3. Select Password protection (1.7) with
4. Press
key to activate password protection.
Î The default password is 1234. To change the password, proceed as follows:
1. In the Start-up (1) menu, select Password (1.8) with
key.
2. Press
key. Select the digit within the password with
3. Press
key. Change the number (0 to 9) within the password with
4. Confirm with
5. After selecting all digits of the password, press
8.1.4
Performing zero calibration
We recommend performing a zero calibration after first start-up and after changes have
been made to the plant.
To set zero, the pressure in the measuring lines must be equal. To check zero, make sure that
the pressures in both measuring chambers are identical at atmospheric pressure, i.e. the sig-
nal at the terminals 31 and 32 must be 4 mA at a differential pressure of ∆p = 0 mbar (see
Fig. 7 on page 37).
At ∆p = 0 mbar, the 0.0 % reading must be displayed.
EB 9510 EN
or
key and confirm with
or
or
key and confirm with
key (proceed in the same way for the rest of the password).
Operation of Media 7 Differential Pressure Meter
key and confirm with
or
key.
or
key.
or
key.
key.
key.
key.
key and confirm with
or
key.
or
key.
61