10 Malfunctions

Malfunctions are indicated on the display by error messages in conjunction with an icon for
status classification and an error ID. The meaning of the icons and their order of priority are
listed in Table 7.
Table 7: Icon showing status classification
Status icon
On the start screen, error messages can be cleared by pressing the
and recommended action for troubleshooting are listed in Table 8.
Table 8: Troubleshooting
Error ID
Message
101
AMR magnet lost
102
AMR sensor not recognized
103
Memory error (calibration)
104
Memory error (data)
105
No factory calibration
106
Pressure sensor error
107
Internal data processing error
201
AMR signal outside range
202
Measuring span error
203
Characteristic error
EB 9510 EN
Priority
1
2
3
4
Possible causes and recommended action
The Media 7 device has an internal device error.
Î Contact SAMSON's After-sales Service.
Î Reset the Media 7 device. Contact
SAMSON's After-sales Service when this
error reoccurs.
Î Check the settings for the tank and media
data. Correct them, if necessary.
An invalid tank geometry has been entered:
Î Re-enter tank data (only possible in TROVIS-
VIEW).
Malfunctions
Meaning
Failure
Out of specification
Maintenance required
No message
key. Error messages
69