Dimensions, Installation and Wiring
4.2

Section

4.3

System Installation Environment

Rexroth IndraControl VDP 80.1 Machine Operator Panel Operator Display
Fig.4-10:
HMI operator panel, section template
When designing the housing for the HMI operator panel, please
take the height of the plug-in connections and the permissible bend‐
ing radius for the cables into consideration.
The HMI operator panel VDP 80.1 has to be handled with care. The housing of
the VDP 80.1 has to be sealed and dust-proof. Only if the housing is sealed
and dust-proof, the VDP 80.1 is protected against coolant splashes or dust
accumulating during machining.
Ambient conditions:
Ambient temperature during operation: 0 ºC to 45 ºC
Storage and transport temperature: –20 ºC to 60 ºC
Changing the ambient temperature: ≤ 1,1 ºC/min
Relative humidity: ≤ 75%
Oscillations: ≤ 0.5 G
Active power: 24 V DC ±10% 2 A
Protection class: IP 54 (system input), IP 00 (system output)
Please note the following points to comply with the afore-mentioned conditions:
The HMI operator panel requires a sealed housing. Sealant has to be ap‐
plied to doors and cable outputs.
The HMI operator panel housing has to be dust-proof and impermeable
to water (also to coolant etc.).
The HMI operator panel housing has to be sufficiently large to ensure heat
dissipation. During operation, the difference between inside and outside
air temperature cannot exceed 10 ºC.
DOK-SUPPL*-VDP*80.1***-PR03-EN-P