● Right-click on "Load cells parameter (DR10)" and select "Send data record".
Figure 7-19
⇒ All parameter settings in DR10 are identical between PC and SIWAREX. All load cell
parameters (DR10) are shown in black.
NOTICE
Parameters overwritten
It is not possible to send or receive individual parameters within a data record. The complete
data record must initially be received for every change to parameters within it. The desired
parameter can then be edited and the data record sent again.
If not all the data can be received from the scale before the parameter change, the active
offline parameters in the scale can be overwritten by the "Send data record" function.
Therefore, proceed as follows:
1. Select the "Receive data record" function.
2. Change the parameters.
3. Select the "Send data record" function.
Run automatic calibration
● After sending the calibration parameters to SIWAREX, select "Automatic calibration" in the
Service menu with an empty scale. Empty scale means only the mechanical dead load (e.g.
empty container) rests on the load cells.
SIWAREX WP321
Operating Instructions, 08/2019, A5E33715669A-AD
SIWATOOL load cell parameters: Send data record
7.4 Fast commissioning (Quick Start) with SIWATOOL
Commissioning
53