7.3.6

Calibrating the scale automatically

The scale can also be calibrated without weights. To do this, it is necessary to enter data
specific to the load cells. In addition, it is essential that the scale is empty.
Figure 7-6
The number of points of support corresponds with a silo, for example, to the number of clamps
or feet of the silo. A quadratic platform scale with a load cell at each corner has 4 support points.
The characteristic values of the individual load cells are required to calculate the average
characteristic value of the cells.
The equation for the calculation is as follows:
(characteristic of cell 1 + characteristic of cell 2 + characteristic of cell n) / n
If the exact characteristic values are unknown, it is permissible to also use rounded-off numbers
(e.g. 1.0 mV/V, 2.0 mV/V). The nominal load of an individual load cell (not the nominal load of
the complete scale!) must subsequently be defined.