Table 3-3 Setpoints - GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series Instruction Manual

Table of Contents

Advertisement

3 SETUP AND USE

Table 3-3 SETPOINTS

Page
Line
1
1
PAGE 1: SETPOINT VALUES
PAGE 1: SETPOINT VALUES
MOTOR AMPS SETPOINTS
MOTOR AMPS SETPOINTS
2
PHASE CT RATIO
PHASE CT RATIO
CT SECONDARY =
CT SECONDARY =
3
PHASE CT RATIO
PHASE CT RATIO
CT PRIMARY = XXXX:X
CT PRIMARY = XXXX:X
4
MOTOR FULL LOAD CURRENT
MOTOR FULL LOAD CURRENT
FLC=
FLC=
5
O/L PICKUP LEVEL
O/L PICKUP LEVEL
LEVEL = 1.05 x FLC
LEVEL = 1.05 x FLC
6
ACCEL.TIME= XXX.X SECONDS
ACCEL.TIME= XXX.X SECONDS
Consult motor data sheet
Consult motor data sheet
7
STARTS/HOUR= X
STARTS/HOUR= X
Consult motor data sheet
Consult motor data sheet
8
UNBALANCE ALARM LEVEL
UNBALANCE ALARM LEVEL
U/B ALARM=
U/B ALARM=
9
U/B ALARM TIME DELAY
U/B ALARM TIME DELAY
TIME DELAY =
TIME DELAY =
10
UNBALANCE TRIP LEVEL
UNBALANCE TRIP LEVEL
U/B TRIP=
U/B TRIP=
11
U/B TRIP TIME DELAY
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
U/B DELAY= XXX SECONDS
12
G/F CT RATIO :5 ? XXX
G/F CT RATIO :5 ? XXX
(NO indicates 2000:1)
(NO indicates 2000:1)
13
GROUND CT PRIMARY
GROUND CT PRIMARY
GROUND CT =
GROUND CT =
14
GROUND FAULT ALARM LEVEL
GROUND FAULT ALARM LEVEL
G/F ALARM=
G/F ALARM=
15
GROUND FAULT ALARM LEVEL
GROUND FAULT ALARM LEVEL
G/F ALARM=
G/F ALARM=
3-18
Setpoints, Pg. 1
Information Line
X AMP
X AMP
XXXX AMPS
XXXX AMPS
XX PERCENT
XX PERCENT
XXX SEC
XXX SEC
XX PERCENT
XX PERCENT
XXX:5
XXX:5
XXX AMPS
XXX AMPS
XXX xCT
XXX xCT
Setpoint Range and Units
:1 or :5
Factory Value = 5
20-1500 (increments of 1)
Factory Value = 100
10-1500 amps (increments of 1)
Factory Value = 10
1.05-1.25 × F LC (increments of
0.01)
Factory Value = 1.05
0.5-125.0 or OFF
(increments of 0.5)
Factory Value = 10.0
1-5 starts or OFF
(increments of 1)
Factory Value = 3
4-30 % or OFF (increments of 1)
Factory Value = 10
3-255 seconds (increments of 1)
Factory Value = 5
4-30 % or OFF
(increments of 1)
Factory Value = 15
3-255 seconds (increments of 1)
Factory Value = 5
YES (5 amp secondary)
or NO (GE Multilin's 50:0.025A
CT w/ ratio of 2000:1)
Factory Value = NO
20–1500 (increments of 1)
(Not seen if ratio is 2000:1)
Factory Value = 100
50:0.025A (2000:1 ratio) CT:
1.-10 amps or OFF
(increments of 1)
Factory Value = 4
5 A secondary CT: 0.1-1.0 xCT
rating or OFF (increments of
0.1)
(not seen if ratio is 2000:1)
Factory Value = 0.4
Manual Ref.
3.7
3.7
3.7
3.18,3.20
3.8
3.9
3.10
3.10
3.10
3.10
3.11
3.11
3.11
3.11