3 SETUP AND USE
Protection of a motor with a service factor that is not
1.0 may use the Overload Pickup Level setpoint to en-
sure the overload curve does not pick up until the de-
sired level. This setpoint determines where the overload
curve picks up as a percent of FLC; it effectively cuts
off the overload curve below the setpoint x FLC.
NOTE: If a new curve number is stored while the
motor is running, the new curve will not come into
effect until the motor has stopped.
3-52