Table 5. Independent Settings For Each Table - GE MOV 2000 Instructions Manual

Digital multifunctional protection, control and supervision relay
Table of Contents

Advertisement

No.
1.
VOLTAGE SETTINGS (V)
1.1
UNDERVOLTAGE
1.2
VOLTAGE ABSENCE
1.3
VOLTAGE PRESENCE
1.4
WEAK INFEED
2.
TIMER SETTINGS
2.1
UNDERVOLTAGE TIMER
2.2
UNDERVOLTAGE' TIMER
3.
25 SETTINGS FOR 521
3.1
DIFF. IN MODULE
3.2
DIFF. IN ANGLE
3.3
DIFF. IN FREQUENCY
3.4
25/ 79 TIMER
3.5
25/ CLOSE TIMER
3.6
79/ DL-DB
3.7
79/ LL-DB
3.8
79/ DL-LB
3.9
79/ SYNCHECK
3.10
CLOSE/ DL-DB
3.11
CLOSE/ LL-DB
3.12
CLOSE/ DL-LB
3.13
CLOSE/ SYNCHECK
4.
25 SETTINGS FOR 520
4.1
DIFF. IN MODULE
4.2
DIFF. IN ANGLE
4.3
DIFF. IN FREQUENCY
4.4
TEMP. 25/ 79
4.5
TEMP.25/ CLOSE
4.6
79/ DL-DB
4.7
79/ LL-DB
4.8
79/ DL-LB
4.9
79/ SYNCHECK
4.10
CLOSE/ DL-DB
4.11
CLOSE/ LL-DB
4.12
CLOSE/ DL-LB
4.13
CLOSE/ SYNCHECK
GEK-106271

TABLE 5. Independent Settings for Each Table

Independent for each table
MIV Digital Multifunctional Protective Relay
Limits
5 - 150 V
5 - 150 V
5 - 150 V
5 - 150 V
0,10 - 20,00 s
0,10 - 20,00 s
1 - 30 V
1º - 60º
0,01 - 2,00 Hz
0,10 - 20,00 s
0,10 - 20,00 s
Dead line – Dead bus Not
Live line – Dead bus
Dead line – Live bus
SYNCHRO CHECK
Dead line – Dead bus Not
Live line – Dead bus
Dead line – Live bus
SYNCHRO CHECK
1 - 30 V
1º - 60º
0,01 - 2,00 Hz
0,10 - 20,00 s
0,10 - 20,00 s
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
permitted / Not
permitted
3. SETTINGS
Default
40 V
10 V
50 V
6 V
1,00 s
1,00 s
10 V
10 º
0,10 Hz
0,50 s
0,50 s
permitted
Not
permitted
Not
permitted
Permitted
permitted
Not
permitted
Not
permitted
permitted
10 V
10 º
0,10 Hz
0,50s
0,50 s
Not
permitted
Not
permitted
Not
permitted
permitted
Not
permitted
Not
permitted
Not
permitted
permitted
23