GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series Instruction Manual page 78

Table of Contents

Advertisement

17
BLOCK PF ALARM & TRIP
BLOCK PF ALARM & TRIP
ON START BY: XXX SECONDS
ON START BY: XXX SECONDS
When enabled, Power Factor alarm and trip protection are blocked from the time the motor starts until
the time delay programmed expires.
1–254 seconds (increments of 1) or OFF (OFF disables this function)
18
PF PROTECTION DELAY
PF PROTECTION DELAY
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
When enabled, after a successful start, the Power Factor must come within range of the Power Factor
lead/lag trip levels for the specified period of time before the Power Factor trip and alarm features be-
come active.
1-254 seconds (increments of 1) or OFF (OFF disables this function)
Factory Value = OFF
19
POWER FACTOR LEAD
POWER FACTOR LEAD
ALARM LEVEL = X.XX
ALARM LEVEL = X.XX
This setpoint is used to set the power factor "lead" alarm threshold level for a power factor alarm condi-
tion.
0.05-0.99 (increments of 0.01) or OFF
Factory Value = OFF
20
POWER FACTOR LAG
POWER FACTOR LAG
ALARM LEVEL = X.XX
ALARM LEVEL = X.XX
This setpoint is used to set the power factor "lag" alarm threshold level for a power factor alarm condi-
tion.
0.05-0.99 (increments of 0.01) or OFF
Factory Value = OFF
21
POWER FACTOR ALARM
POWER FACTOR ALARM
TIME DELAY = XXX
TIME DELAY = XXX
This setpoint is used to set the time delay that a power factor alarm condition must persist for in order to
facilitate an alarm.
1-255 seconds (increments of 1)
Factory Value = 10
22
POWER FACTOR LEAD
POWER FACTOR LEAD
TRIP LEVEL = X.XX
TRIP LEVEL = X.XX
This setpoint is used to set the power factor "lead" trip threshold level for a power factor trip condition.
0.05-0.99 (increments of 1) or OFF
Factory Value = OFF
Setpoints, Pg. 7