3 SETUP AND USE
24
TIME BETWEEN STARTS
TIME BETWEEN STARTS
TIME DELAY = XXX MIN
TIME DELAY = XXX MIN
This setpoint is used to inhibit the current start attempt if the time specified has not elapsed since the
most recent start.
1-254 (increments of 1) or OFF - time delay in minutes (OFF disables this function)
Factory Value = OFF
25
FLC THERMAL CAPACITY
FLC THERMAL CAPACITY
REDUCTION = XX PERCENT
REDUCTION = XX PERCENT
This setpoint is used to program the level which the thermal memory will discharge to when the motor is
running at full load current. This level may be set as the percentage difference of the hot motor thermal
damage curve to the cold motor thermal damage curve. See section 3.20.
[
TCR =
(Hot motor stall time)
1
(Cold motor stall time)
Range: 0% - 90% increments of 1% (0 disables this feature)
Factory Value = 15%
26
THERMAL CAPACITY USED
THERMAL CAPACITY USED
ALARM LEVEL = XXX%
ALARM LEVEL = XXX%
This setpoint is used to set the level to which the thermal capacity will be compared. If the thermal ca-
pacity equals or exceeds this setpoint for the specified time delay, an alarm will occur (see section 3.19).
Range: 1% - 100% increments of 1%, or OFF
Factory Value = OFF
27
THERMAL CAPACITY USED
THERMAL CAPACITY USED
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
This setpoint is used to set the time delay for operation of the Thermal Capacity Alarm function.
Range: 1 - 255 sec (increments of 1)
Factory Value = 5
28
END OF PAGE FIVE
END OF PAGE FIVE
SETPOINT VALUES
SETPOINT VALUES
3-32
Setpoints, Pg. 5
]
×