GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series Instruction Manual page 73

Table of Contents

Advertisement

3 SETUP AND USE
6
STATUS = XXXXXX
STATUS = XXXXXX
FOR: XXXXXXXXXXXX SWITCH
FOR: XXXXXXXXXXXX SWITCH
This line can be used to check the status (either OPEN or SHORT) of any of the following terminals:
EXT.RESET, EMG.RESTART, ACCESS, SPEED, DIFF., or SPARE
7
SOFTWARE ACCESS = OFF
SOFTWARE ACCESS = OFF
ACCESS STATUS: ENABLED
ACCESS STATUS: ENABLED
This line will display the access status as ENABLED or DISABLED, reflecting whether setpoints may be
stored or not. Storing a value of OFF for "Software Access" defeats the software access feature. Access
is then strictly a function of the access jumper. Once the status reflects ENABLED, a value may be
stored for "Software Access". This value (1–500) will activate the software access feature. The value
stored will remain on the screen until the user moves to a new line, presses the CLEAR button, or ac-
cess becomes disabled. The display of the Software Access code will then revert to "0" so that the code
cannot be viewed (a value of "0" may never be stored for this setpoint). The Access Status will remain
enabled for approximately 4 minutes after the last key is pressed, or until the access jumper is removed.
To enable access again, the user must ensure the access jumper is installed and then store his software
access code.
0–500, in increments of 1, or OFF (A value of OFF disables the Software Access feature. A value of "0"
Factory Value = OFF.
8
SERVICE USE ONLY
SERVICE USE ONLY
CODE = XX
CODE = XX
This line is used by GE Multilin service personnel for calibration and service to the 269 relay.
9
CAN.SERVICE: 905-294-6222
CAN.SERVICE: 905-294-6222
http://www.ge.com/edc/pm
http://www.ge.com/edc/pm
Canadian service phone number and web site address.
10
ENCRYPTED SECURITY
ENCRYPTED SECURITY
ACCESS CODE = XXX
ACCESS CODE = XXX
In the event that the user should forget or lose his Software Access code, the value displayed on this line
may be used by a GE Multilin Service person to decipher and notify the user of his Software Access
code.
11
MULTILIN 269 RELAY
MULTILIN 269 RELAY
REVISION
REVISION
This is the 269 relay firmware revision identifier line.
12
269 SERIAL NUMBER
269 SERIAL NUMBER
SERIAL #: D20 X XXXX
SERIAL #: D20 X XXXX
This is the 269 relay serial number identifier, where:
D: Hardware revision
20: Product code
X: Last digit of production year
XXXX: Four digit serial number
3-34
Setpoints, Pg. 6
indicates that the feature is enabled).
269.XX.X