3.2 Apply Power to the Gateway or Node

Integral 5-pin M12/Euro-style quick disconnect wiring depends on the model and power requirements of the device. Not all
models can be powered by 10 to 30 V dc and not all models can be powered by 3.6 to 5.5 V dc. Refer to
verify the power requirements of your device.
5-pin M12
1
2
4
3
5
1. Apply power to the Gateway by connecting the 10 to 30 V dc cable as shown.
The Gateway begins in RUN mode, displays the current network ID (NID), then identifies itself as a Gateway.
2. Apply power to the Node by connecting the 10 to 30 V dc cable or the DX81 Battery Supply Module as shown. To
apply power to a FlexPower Node with an integrated battery, install the battery into the housing.
The Node starts in RUN mode, displays the current network ID, then identifies itself as a Node and lists its device ID.

3.3 Bind Radios to Form Networks

Binding Nodes to a Gateway ensures the Nodes only exchange data with the Gateway they are bound to. For a more
detailed definition of binding mode, refer to the
manual.
Apply power to the Gateway and Nodes.
2 For FlexPower devices, do not apply more than 5.5 V dc to the gray wire.
14
Pin
Wire Color
Gateway (10 to 30 V dc) Node (10 to 30 V dc)
1
brown
10 to 30 V dc input
2
white
RS485 / D1 / B / +
3
blue
dc common (GND)
4
black
RS485 / D0 / A / -
5
gray
Comms gnd
Advanced Setup section of the SureCross Wireless I/O Networks instruction
www.bannerengineering.com - Tel: + 1 888 373 6767
Sure Cross DX80 Node
(150 mW radio)
10 to 30 V dc
dc common (GND)
Sure Cross Performance Node
(in 250 mW mode)
Specifications to
Node (FlexPower)
dc common (GND)
3.6 to 5.5 V dc 2