Banner Sure Cross DX80 Series Instruction Manual page 54

Wireless i/o networks
Table of Contents

Advertisement

®
Sure Cross
Performance DX80 Wireless I/O Networks
Install or Replace the Battery (DX99...D Models)
WARNING:
Do not replace battery when an explosive dust atmosphere may be present.
The replacement battery MUST be a Banner approved battery, model number BWA-BATT-001.
Use of a different battery will VOID the intrinsic safety rating of this device and may result in an
explosion!
When replacing the battery, the negative end of the battery holder is the side by the large
capacitors. This side is marked with a minus (−) sign.
Do not attempt to recharge the battery. These batteries are not rechargeable. Recharging may
cause serious injury to personnel or damage the equipment. Replace only with factory
recommended batteries.
To install or replace the lithium "D" cell battery in the metal housings, follow these steps.
1. Unscrew the lid of the metal enclosure.
2. Lift the radio out of the metal enclosure and pull the spacer frame off the back side of the radio.
3. Disconnect the radio by unplugging the ribbon cable from the radio board and set aside the radio and spacer frame.
4. If you are replacing an existing battery, remove the discharged battery.
5. Insert a new battery. Only use a 3.6 V lithium battery from Xeno, model number XL-205F.
6. Verify the battery's positive and negative terminals align to the positive and negative terminals of the battery holder
mounted within the case. Caution: There is a risk of explosion if the battery is replaced incorrectly.
7. Wait two minutes.
8. Insert the ribbon cable through the center of the spacer frame, then plug the ribbon cable back into the radio board.
9. Insert the radio back onto the spacer frame pins. Push the radio and spacer frame assembly back into the enclosure
until it is seated.
10. Screw on the lid and tighten.
11. After replacing the battery, allow up to 60 seconds for the device to power up.
12. Properly dispose of your used battery according to local regulations by taking it to a hazardous waste collection
site, an e-waste disposal center, or other facility qualified to accept lithium batteries.
54
As with all batteries, these are a fire, explosion, and severe burn hazard. Do not burn or expose
them to high temperatures. Do not recharge, crush, disassemble, or expose the contents to
water.
Replacement battery model number: BWA-BATT-001. For pricing and availability, contact
Banner Engineering.
As with all batteries, these are a fire, explosion, and severe burn hazard. Do not burn or
expose them to high temperatures. Do not recharge, crush, disassemble, or expose the
contents to water.
The battery may be replaced in explosive gas atmospheres. Replacement battery model
number: BWA-BATT-001. For pricing and availability, contact Banner Engineering.
www.bannerengineering.com - Tel: + 1 888 373 6767

Advertisement