Advertisement

The following table shows the pneumatic connection versions for different actuator types,
regulating action and safety position after an auxiliary power supply failure.
Actuator type
Single-acting
Double-acting
5.4

Restrictors

● Reduce the air output to achieve travel times of T > 1.5 s for small actuators. Use restrictors
Y1
● When turned clockwise, they reduce the air output and finally shut it off.
● In order to set the restrictors, we recommend closing them and then opening slowly.
● In case of double-acting valves, ensure that both restrictors have approximately the same
setting.
Figure 5-13
*) Restrictor Y2
See also
Sequence of automatic initialization (Page 111)
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Response to failure of auxiliary power: The ac‐
tuator moves into safety position
Failure of electrical
Failure of pneumatic
auxiliary power
auxiliary power
Y1 = vented
Y1 = vented
Y1 = pressurized
Y1 = closed
Y2 = vented
Y2 = closed
and Y2
for this purpose.
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators *)
Hexagon socket-head screw 2.5 mm
Restrictors
is not active for single-acting Fail in Place F01
Fail in place, order suffix F01
Failure of electrical
Failure of pneumatic
auxiliary power
auxiliary power
Y1 = closed
Y1 = closed
Y1 = closed
Y1 = closed
Y2 = closed
Y2 = closed
Connect
5.4 Restrictors
95