Siemens SIPART PS2 Operating Instructions Manual page 137

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter
Function
39.BIN1
Function binary input 1
2)
None
Message only
Block configuration
Block configuring and manual operation
Move valve to position YE
Move valve to position YA
Block movement
Partial stroke test
40.BIN2
Function binary input 2
2)
None
Message only
Move valve to position YE
Move valve to position YA
Block movement
Partial stroke test
41.AFCT
Alarm function
3)
None
A1 = Min, A2 = Max
A1 = Min, A2 = Min
A1 = Max, A2 = Max
42.A1
Response threshold, alarm 1
43.A2
Response threshold, alarm 2
44. FCT
Fault message function
3)
Fault
Fault + not automatic
Fault + not automatic + BIN
45. TIM
Monitoring period for setting the fault message
'Control deviation'
46. LIM
Response threshold of fault message 'Control
deviation'
47. STRK
Limit monitoring for the number of total strokes
48.PRST
Preset
Reset all parameters which can be reset
by 'Init', 'PArA' and 'diAg'.
Reset initialization parameters '1.YFCT'
to '5.INITM'.
Reset parameters '6.SDIR' to '47. STRK'
and '51.FSTY' to '53.FSVL'.
Reset parameters A to P of the extended
diagnostics function as well as parame‐
ter '50.XDIAG'.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Parameter values
4)
4)
8.2 Tabular overview of the parameters
NO contact
OFF
on
bloc1
bloc2
uP
doWn
StoP
PST
NO contact
OFF
on
uP
doWn
StoP
PST
Normal
OFF
0.0 ... 10.0 ... 100
0.0 ... 90.0 ... 100
Normal
Auto / 0 ... 100
Auto / 0 ... 100
0 ... 1.00E9
ALL
Init
PArA
diAg
Parameter assignment
Unit
NC contact
-on
-uP
-doWn
-StoP
-PST
NC contact
-on
-uP
-doWn
-StoP
-PST
Inverted
%
%
Inverted
s
%
137