Installing/mounting
4.5 Installing the optional modules
6. Screw the special screw
screw
Note
Pin in the actuating disk bearing
A pin
1. Align pin
2. Rotate the actuating disk bearing
7. Set the limits L1 and L2 as described below.
8. An insulating cover (yellow) is required over the module. This insulating cover is supplied
with the module. Place the insulating cover on one side under the basic electronics seat of
the rack. The recesses of the insulating cover must fit in the corresponding webs of the rack.
To tighten the insulating cover, bend the walls of the adapter slightly outwards.
Firmly press the other end until the insulating cover is underneath the contact surface of the
basic electronics. The recesses of the insulating cover must fit in the corresponding webs
of the rack.
9. Place the basic electronics onto the four holders of the rack.
10.Tighten the two fixing screws of the basic electronics. Tighten the screws.
11.Reestablish all electrical connections between the basic electronics and the option modules.
12.Connect the basic electronics with the option modules and the potentiometer. Use the
corresponding ribbon cables.
13.Put on the supplied module cover. Make sure that the ribbon cable is not trapped.
Note
Module cover
Do not use the standard module cover. The provided module cover has a larger recess.
14.Close the positioner as described in section "Closing the standard and and intrinsically safe
version (Page 55)".
Procedure: Setting the limits L1 and L2
1. Move the actuator to the first desired mechanical position.
2. Adjust the upper actuating disk
changes. Set a high-low or a low-high switchover as follows:
– Rotate the actuating disc beyond the switching point until you reach the next switching
68
with a torque of 2 Nm.
is pressed in the actuating disk bearing
with the groove of the special screw before inserting the head of the special
screw
into the actuating disk bearing
pin
is inserted into the groove of the special screw
point.
through the module into the positioner shaft. Tighten the special
.
and the special screw
manually until the output signal at terminals 51 and 52
Operating Instructions, 05/2019, A5E00127926-AC
.
simultaneously so that the
.
SIPART PS2 with PROFIBUS PA

Advertisement