Monitoring Of Number Of Total Strokes 'L.\\Strk - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
8.3 Description of parameters
J4.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
8.3.3.10

Monitoring of number of total strokes 'L.\\STRK'

L. STRK - Monitoring of number of total strokes
Condition:
Possible settings:
Purpose:
Factory setting:
L1.LIMIT - Limit
Adjustment range:
Purpose:
Factory setting:
182
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a threshold 3 message if the current tem‐
perature inside the enclosure exceeds threshold 3. The process to
activate and display this message is described in the 'XDIAG' pa‐
rameter.
90.0C
The '50.XDIAG' Activation of extended diagnostics (Page 160) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
● OFF
● On
Use this parameter to continuously monitor the total strokes cov‐
ered by the actuator. A total stroke corresponds to the path from the
lower endstop of the actuator to the upper endstop and back again,
in other words twice the travel. During operation, partial strokes of
the actuator are added together into total strokes. Monitoring is
performed in three steps. To activate monitoring, set the parameter
to 'On'. Sub-parameters are displayed. Appropriately set the sub-
parameters.
The current value is displayed in Diagnostic value '1.STRKS - Num‐
ber of total strokes' (Page 259). The positioner triggers a message
if the current value exceeds one of the three thresholds. This mes‐
sage is only output if threshold 2 or 3 is not exceeded at the same
time.
OFF
1 ... 1.00E8
Use this sub-parameter to set the base limit for the number of total
strokes. Set the base limit in a range from '1' to '1.00E8'.
1.00E6
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC