Note
Leakage
Besides continuous air consumption, a leakage can cause the positioner to try to compensate
the position deviation. This will result in premature wear in the entire control device.
● Check offline using the diagnostic parameter "11.LEAK" whether leakage is present.
● If there is leakage, check the pneumatic connections for leaks.
See also
Changing the operating mode (Page 101)
Diagnostic value '11.LEAK - Leakage test' (Page 261)
5.3.2

Pneumatic connection in non-flameproof enclosure

5.3.2.1

Structure of pneumatic connection

*) for double-acting actuators
Figure 5-11
5.3.2.2

Integrated pneumatic connection

The following pneumatic connections are provided at the rear side of the basic device for the
integrated attachment for single-acting linear actuators:
● Actuating pressure Y1
● Exhaust air outlet
These connections are sealed with screws when the device is delivered.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Output: Actuating pressure Y2 *)
Input: Supply air PZ
Output: Actuating pressure Y1
Exhaust air outlet with sound absorber, thread G¼
Pneumatic connection, example
Connect
5.3 Pneumatic connection
93