J3.LEVL2 - threshold 2

Adjustment range:
Purpose:
Factory setting:
J4.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
9.4.3.10

Monitoring the number of total strokes 'L.\\STRK'

L. STRK - Monitoring the number of total strokes
Requirement:
Possible settings:
Purpose:
Factory setting:
194
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a message if the current temperature inside
the enclosure overshoots threshold 2. The process to activate and
display this message is described in the 'XDIAG' parameter.
80.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 3. The process to activate
and display this message is described in the 'XDIAG' parameter.
90.0C
The '52.XDIAG' Activating for extended diagnostics (Page 174)
parameter is set to 'On1', 'On2' or 'On3'.
• OFF
• On
Use this parameter to continuously monitor the total strokes cov-
ered by the actuator. A total stroke corresponds to the path from
the lower endstop of the actuator to the upper endstop and back
again, in other words twice the travel. During operation, partial
strokes of the actuator are added together into total strokes. Moni-
toring is performed in three steps. To activate monitoring, set the
parameter to 'On'. Sub-parameters are displayed. Appropriately
set the sub-parameters.
The current value is displayed in Diagnostic value '1.STRKS -
Number of total strokes' (Page 211). The positioner triggers a
message if the current value exceeds one of the three thresholds.
This message is only output if threshold 2 or 3 is not exceeded at
the same time.
OFF
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB