14.30 Dry Concrete

Purpose
Provide heat to floor heating panel and dry the wet concrete during installation.
Setting condition:
Dry concrete parameter can be set through remote control under system setup.
o
Parameters are possible to set up to 99 days with different target set temperature
o
Control details:
Dry concrete mode will be activates when select ON from service setup.
o
Once start dry concrete function, remote control will send step 1 setting temperature to indoor unit.
o
* This temperature is set at zone temperature. If system is 2 zones, both zone target temperature is set as
same temperature.
Heat pump will start heat mode operation to room side with received target water outlet temperature.
o
* Heat pump will operate according to Heat pump Target Water Temperature.
After complete day 1 setup operation, day 2 data will be send to indoor at 12.00am on the second day.
o
Each preset data will be send every day until dry concrete mode is complete, unit will turns OFF and exit dry
o
concrete function.
3 ways valve and booster heater will turn OFF and 2 ways valve will turns ON.
o
Cancel condition:
Dry concrete mode is complete and OFF signal is received.
o
OFF signal is received by pressing OFF/ON button.
o

14.31 Flow Sensor

The water flow sensor serves as an overload protector that shuts down the unit when the water level is detected
to be low.
Abnormal flow detection:
Sequence
Normal case
During status 2~6 on Anti-freeze deice
Abnormal flow
Flow rate < 7 l/min or ≥ 69 l/min
Flow rate ≥ 7 l/min
163
Normal flow
≥ 7 l/min
< 7 l/min