Panasonic WH-UD05JE5 Service Manual page 207

Air-to-water hydromodule + tank
Hide thumbs Also See for WH-UD05JE5:
Table of Contents

Advertisement

19.5.18 Indoor Backup Heater OLP Abnormality (H70)
Malfunction Decision Conditions:
During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit.
Malfunction Caused:
1
Faulty power supply connector connection.
2
Faulty connector connection.
3
Faulty indoor backup heater overload protector (OLP).
4
Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 60 seconds.
Troubleshooting:
Is the abnormality happened during
operation of indoor backup heater?
Yes
Check the indoor backup heater incoming
AC power supply (2):
- Turn ON power supply (2) & RCCB.
- Measure the AC voltage between RCCB's
L1 & N1.
- Measure the AC voltage between PCB's
AC2-L3 & AC2-N2.
Is measured voltage 230Vac?
Yes
Check the CN-OLP1 connector connection:
- Turn OFF the power.
- Check the connector connection.
Is the CN-OLP1 connector
connection normal?
Yes
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Caution
No
- Defect in indoor unit PCB (main).
- Replace the indoor unit PCB (main).
- Defect in RCCB.
- Replace RCCB.
- Terminal board assembly
No
connector poor contact.
- Correct the connection or
replace the indoor unit
PCB (main).
No
- Connector poor contact.
- Correct the connection.
207
Check indoor backup heater OLP
continuity:
- Turn OFF power supply.
- Reset heater 1 OLP.
- Measure the continuity of OLP.
Is there any continuity?
No
Yes
Use a test pen to push
this button to reset OLP
Multimeter to
measure continuity
- Defect in indoor backup
heater OLP.
- Replace indoor backup
heater OLP.
- Defect in indoor unit
PCB (main).
- Replace the indoor unit
PCB (main).