If start condition is fulfilled, indoor will receive the voltage signal from optional PCB. Indoor will send the rate
value to outdoor unit.
Outdoor will change the current limit according to the percentage receive from indoor unit.

12.28 Holiday Mode

Purpose:
Promotes energy saving by allowing the user to stop the system during holiday and enables the system to
resume at the preset temperature after holiday.
Control details:
Indoor operate the unit according running mode request. Target temperature will follow holiday setting
o
temperature.
If heat mode request is receive, Target Water Out Temperature will change according to holiday shift
temperature set.
[If heat is set OFF at holiday, unit, water pump and zone control will OFF]
If tank mode request is receive, Target Tank Set Temperature will change according to the holiday tank
shift temperature set.
[If tank is set OFF at holiday, heat pump and tank heater will OFF]
After days of holiday have been set, heat pump will stop and only resume operation at the end of holiday
o
countdown.
Start condition:
Holiday timer set and the holiday timer start
o
* The day holiday mode was set is counted as day 1.
Stop condition:
OFF/ON button is pressed.
o
Holiday timer is reached.
o

12.29 Dry Concrete

Purpose
Provide heat to floor heating panel and dry the wet concrete during installation.
Setting condition:
Dry concrete parameter can be set through remote control under system setup.
o
Parameters are possible to set up to 99 days with different target set temperature
o
Control details:
Dry concrete mode will be activates when select ON from service setup.
o
Once start dry concrete function, remote control will send step 1 setting temperature to indoor unit.
o
* This temperature is set at zone temperature. If system is 2 zones, both zone target temperature is set as
same temperature.
Heat pump will start heat mode operation to room side with received target water outlet temperature.
o
* Heat pump will operate according to Heat pump Target Water Temperature.
After complete day 1 setup operation, day 2 data will be send to indoor at 12.00am on the second day.
o
Each preset data will be send every day until dry concrete mode is complete, unit will turns OFF and exit dry
o
concrete function.
3 ways valve and booster heater will turn OFF and 2 ways valve will turns ON.
o
Cancel condition:
Dry concrete mode is complete and OFF signal is received.
o
OFF signal is received by pressing OFF/ON button.
o

12.30 Flow Sensor

The water flow sensor serves as an overload protector that shuts down the unit when the water level is detected
to be low.
Abnormal flow detection:
Sequence
Normal case
During status 2~6 on Anti-freeze deice
Abnormal flow
Flow rate < 7 l/min or ≥ 69 l/min
Flow rate ≥ 7 l/min
124
Normal flow
≥ 7 l/min
< 7 l/min