Indoor Unit
9 : Terminal Board No.
Control Content:
External room thermostat control activate only when remote thermostat connection select YES by Indoor control
panel.
When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running cool
mode, refer thermo On/Off from cooling line feedback.
Heat pump Off immediately when receive thermo off feedback.

14.22 Three Ways Valve Control

Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side.
Control contents:
1
3 ways valve switch Off:
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
o
2
3 ways valve switch On:
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
o
3
Stop condition:
During stop mode, 3 ways valve will be in switch off position.
o
Indoor Unit
AC230V
* During pump down and force mode, fix 3 ways valve in close condition.
* Recommended Parts : SFA 21/18 (Siemens)
9
10
Cooling
11
Heating
12
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
Spring Return 2 point
NC
1
L
1
L
3
N1
3
5
N1
N2
5
N2
NO
1
L
3
N1
5
N2
L (label)
Y1 (label)
Y2 (label)
1
M
3
5
6: Terminal Board No.
M
156
Siemen RAA20
SPDT 3 wire
COM
L
M
Open
N1
Close
N2