Panasonic WH-UD05JE5 Service Manual page 228

Air-to-water hydromodule + tank
Hide thumbs Also See for WH-UD05JE5:
Table of Contents

Advertisement

19.5.39 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet
temperature sensor 2 are used to determine sensor error.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 5 seconds.
Troubleshooting:
Indoor Refrigerant Liquid / Water Inlet / Water
Outlet Sensor Characteristic
120
110
100
90
80
70
60
50
40
30
20
10
0
-10
0
10
20
30
Temperature (°C)
Caution
Check the CN-TH3 connector connnection:
- Turn OFF the power.
- Check the connector connection.
Is the CN-TH3 connector
connection normal?
Check the indoor water outlet temperature sensor:
- Plug out connector from the indoor unit PCB.
- Measure the resistance of the indoor water outlet
temperature sensor.
Is the measured resistance of the
indoor water outlet temperature
sensor matches the value specified
in its characteristic chart?
40
50
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
No
Yes
No
Yes
228
- Connector poor contact.
- Correct the connection.
- Defect in indoor water outlet
temperature sensor.
- Replace the indoor water
outlet temperature sensor.
- Defect in indoor unit PCB.
- Replace the indoor unit PCB.