15. Protection Control (WH-UD03JE5 WH-UD05JE5)

15.1

Protection Control for All Operations

15.1.1 Time Delay Safety Control
1
The compressor will not start for three minutes after stop of operation.
15.1.2 30 Seconds Forced Operation
1
Once the compressor starts operation, it will not stop its operation for 30 seconds.
2
However, it can be stopped using control panel at indoor unit.
15.1.3 Total Running Current Control
1
When the outdoor running current exceeds X value, the compressor frequency will decrease.
2
If the outdoor running current does not exceed X value, the compressor frequency will return to normal
operating frequency.
3
If the outdoor running current continue to increase till exceed Y value, compressor will stop, and if this occurs
3 times within 20 minutes, system will stop operation and OFF/ON control panel LED will blink (F16 error
occurs).
Heating
Cooling
A. DC Peak Current Control
1
When the current to IPM exceeds set value, compressor will stop. Compressor will restart after three minutes.
2
If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart
after two minutes.
3
If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON
control panel LED will blink (F23 error occurs).
15.1.4 Compressor Overheating Prevention Control
The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in
below figures. When the compressor tank temperature exceeds 112°C, compressor will stop, and if this occurs
4 times within 30 minutes, system will stop operation and OFF/ON control panel LED will blink (F20 error occurs).
Operation Mode
X (A)
11.0
7.0
112°C
110°C
108°C
Compressor tank temperature
UD03JE5
Y (A)
X (A)
14.0
11.0
14.0
8.3
Compressor = OFF
Compressor
Frequency Reduced
Compressor
Frequency Maintain
Free
164
UD05JE5
Y (A)
14.0
14.0
97°C
97°C
97°C