Basic Operation
This section explains the basic settings required to operate and stop the
Inverter.
The settings of parameters described here will be sufficient for simple In-
verter operations.
First, make these basic settings, then skip to the explanations of those spe-
cial functions, even when your application requires special functions, such
as stall prevention, carrier frequency setting, overtorque detection, torque
compensation, slip compensation. Refer to Chapter 6 Advanced Opera-
tion .

5-1 Initial Settings

The following initial settings are required.
Parameter Write-prohibit Selection/Parameter Initialization (n01): Set n01 to 1 so
that n01 through n79 can be set or displayed.
Rated Motor Current (n32): Check the rated current on the motor nameplate and set
the parameter.
Setting the Parameter Write-prohibit Selection/Parameter
Initialization (n01)
Set n01 to 1 so that n01 through n79 can be set or displayed.
Parameter Write-prohibit Selection/Parameter
n01
Initialization
Setting
0, 1, 6, 8, 9
range
Note This parameter makes it possible to write-prohibit parameters, change the pa-
rameter set or displayed range, or initialize all parameters to default values.
Set Values
Value
0
Only n01 can be displayed and set. The n02 through n79 parameters can be
displayed only.
1
The n01 through n79 parameters can be displayed and set.
6
Only the error log memory is cleared.
8
Enables the initialization of all parameters in 2-wire sequence so that the
parameters will return to default values.
9
Enables the initialization of all parameters in 3-wire sequence.
5-2
Changes during
operation
Unit of
1
Default setting
setting
Description
Chapter 5
No
1