6-4 Overtorque Detection Function

When an excessive load is applied to the equipment, the Inverter detects
the overtorque condition through an increase in the output current.
Overtorque Detection Function Selection
n59
Setting
0 to 4
range
Set Values
Value
0
Inverter does not monitor overtorque.
1
Inverter monitors overtorque only when speed is matched. It continues
operation (issues warning) even after overtorque is detected.
2
Inverter monitors overtorque only when speed is matched. It discontinues
operation (through protective function) when overtorque is detected.
3
Inverter always monitors overtorque during operation. It continues operation
(issues warning) even after overtorque is detected.
4
Inverter always monitors overtorque during operation. It discontinues
operation (through protective function) when overtorque is detected.
Set n60 for overtorque detection level and n61 for overtorque detection time to enable
the overtorque detection function. The Inverter will detect overtorque when the current
the same as or higher than the detection level is output for the preset detection time.
Set n40 for multi-function output to either of the following so that external overtorque
detection output will be ON.
Set Value: 6 for overtorque detection (NO)
Set Value: 7 for overtorque detection (NC)
Overtorque Detection
Output
current
Overtorque detection time
Overtorque
detection (NO)
Note
Overtorque detection will be canceled if the output current decreases from the detection level by approx-
imately 5% of the Inverter rated current.
Unit of
1
setting
Description
See note.
n61
Chapter 6
Changes during
No
operation
Default setting
0
n60 (Overtorque
detection level)
Time
Time
6-9