Basic Operation
Setting the Rated Motor Current (n32)
Set the rated motor current (n32) in order to prevent the motor from burning due to over-
loading.
Check the rated current on the motor nameplate and set the parameter.
This parameter is used for the electronic thermal function for motor overload detection
(OL1). By setting the correct parameter, the overloaded motor will be protected from
burning.
Rated Motor Current
n32
Setting
0.0% to 120% (A) of rated
range
output current of Inverter
Note 1. The standard rated current of the maximum applicable motor is the default
rated motor current.
Note 2. Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
Changes during
operation
Unit of
0.1 A
Default setting
setting
Chapter 5
No
(see
note 1)
5-3