Santak CASTLE Series User Manual page 18

Hide thumbs Also See for CASTLE Series:
Table of Contents

Advertisement

Model
EMC Standard
National standard
Industry standard
Operation
Store temperature
Relative humidity
Altitude
① When ambient temperature<30℃, Output power factor can be changed to
0.9 through the serial command,Default power factor is 0.8.
Note:If the UPS is used above elevation 1000M , the derating rating must
be used, and the derating factor is shown in the following table.
High altitude load = Rated power × Derating coefficient(Corresponding to elevation)
Elevation(m)
Derating
Rack1K Rack1KS Rack2K Rack2KS Rack3K Rack3KS
GB7260.2
GB 4943.1-2011
YD/T 1095-2008
PF=0.8 0℃~40℃ PF=0.9 0℃~30℃
1000
100%
GB 7260.1-2008,EN62040-1
CQC 3108-2011
-25℃~55℃
20%~90%(non-condensing)
<1000m
1500
95%
- 16 -
IEC 62040-2-2005
2000
91%