Technical Data

B.3 21/24-Cell Specifications

B.3

21/24-Cell Specifications

Cells in Drive
(without Reduncancy)
21, 24
Parameters
Input Line Voltage
Input Frequency
Input Power Factor
Input Harmonics
Inverter Efficiency
Output Voltage
Output HVF
Output dv/dt
Overload Capacity
Output Frequency
Output Torque
Auxiliary Voltage
Enclosure Type
Degree of Protection
Ambient Temperature
Altitude
Cooling
112
Output Voltage
Available L-L (with O-M)
10 kV/11 kV
Ratings
3.3 - 13.8 kV;
3-phase; +10%/-10%
50 or 60 Hz ± 5%
≥ 0.96 fundamental and ≥ 0.95 above 10% load
Meet IEEE519 (at full output current) requirements at the drive MV input terminals and under
the assumption of full balanced incoming voltages and pre-existing voltage distortion < 2%.
A short circuit ratio < 20 with the VFD operating at nominal speed and rated power is as‐
sumed.
≥ 98.5%
21/24 Cells
10 kV/11 kV
< 0.03
< 3000 V/µS
110% 1 minute / 10 minutes
0.5 Hz ~ 330 Hz
(0.5 Hz ~ 110 Hz for 21-Cell system)
10 ~ 167 Hz (2 - Quadrant)
(10 ~ 110 Hz for 21-Cell system)
380 V 3AC, 50 / 60 Hz ± 10% continuous operation
Ventilated
Standard: IP31 (Not including blower cage)
Optional: IP42 (Not including blower cage)
5 - 40 °C (maximum 50 °C, derating starts from 40 °C on)
Altitude up to 1000 m (3300 ft) – Standard with no output power de-rating.
Altitude above 1000 m (3300 ft) to 2000 m (6600 ft) – Standard output current de-rating.
Altitude above 2000 m (6600 ft) to 4500 m (14850 ft) – De-rating
Ventilated, forced air-cooled with integrated fans
KVA Range
250 - 5250
Operating Instructions, 07/2018, A5E42736645A_AB