Cooling Section; Application Of Voltage; Blowers And Speed Settings - Siemens SINAMICS PERFECT HARMONY GH180 Operating Instructions Manual

Medium voltage variable frequency drive, air cooled 6sr5
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Description
4.1 Cabinet Details
Ethernet Port
Ethernet Port is included on the front of the control door. The port can be used for debug
support and uploading / dowloading data communications with the NXG controller.
Note
Use of Ethernet Port
This port is for maintenance use only. This port is secured by physical access only. Connection
of this port to any network is strongly discouraged.
4.1.6

Cooling Section

Cooling System Components
The cooling system consists of several parts including blower(s). Each blower has a suitably
rated three-phase combination starter (circuit breaker & contactor combination). There is an
optional line reactor that is connected upstream to the combination starter in the circuit that
feeds an EMI filter.
Cooling System Function
The cooling system functions as follows:
● The line reactor connects to a combination starter (circuit breaker & contactor combination).
The contactor is controlled through the SOP of the NXG controller.
● The output of the combination starter (circuit breaker & contactor combination) connects
to quick disconnect plugs which connect individual blowers to the power source.
● The default SOP logic is configured to operate the blower immediately when control power
is energized.
● If the blower (or blowers) fails or loses power, the SOP logic controller issues a drive trip.
This fault condition must be manually reset.
4.1.6.1

Application of Voltage

Control power must always be applied prior to application of medium voltage.
4.1.6.2

Blowers and Speed Settings

Blowers
All SINAMICS PERFECT HARMONY GH180 air-cooled drives are force air-cooled.
An extremely important part of the installation process is making provisions for exhausting the
heat that is generated by the operation of the drive. Although the drive is highly efficient, there
24
Operating Instructions, 07/2018, A5E42736645A_AB
Air Cooled 6SR5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents