Commissioning
8.1
Residual Current Device (RCD) Compatibility
RCD Incompatibility
Connecting this device to a power supply protected by a residual-current device can result
in damage to property and minor personal injury.
This product can produce a DC current in the grounding conductor.
When using a Residual Current Device (RCD) in cases where direct or indirect contact can
be made, only a Type-B RCD shall be permissible on the line side of this product. If this is
not possible, an alternative means of protection must be applied. Isolation from the
environment through double or reinforced insulation, or isolation from the power supply using
a transformer, is an example of alternative means of protection.
Air Cooled 6SR5
Operating Instructions, 07/2018, A5E42736645A_AB
CAUTION
8
67