External Actual Temperature 2; Fault, Actual Temperature - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

10.3.7
External actual temperature
Number
7
2-byte communication object for reading an external temperature value provided via the KNX
bus.
10.3.8

External actual temperature 2

Number
8
2-byte communication object for reading an additional external temperature value provided via
the KNX bus.
10.3.9

Fault, actual temperature

Number
9
If one of the parameterized input temperatures is unavailable to the controller for a period longer
than the monitoring time, the controller enters the error mode. The error mode is sent to the bus
as the value 1.
Note
About item 2:
This object must be connected to the "Fault, actual temperature (slave)" object
in order to indicate the error mode.
About item 3:
This object must be connected to the "Fault, actual temperature (slave)" object
in order to indicate the error mode.
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Name
External actual temperature
Name

External actual temperature 2

Name
1. Fault, actual temperature
2. Fault, actual temperature
(master)
3. Fault, actual temperature
(slave)
Communication objects - RTC
Object function
Input
Object function
Input
Object function
Output
Output
Output
Data type
2-byte floating point
value
Data type
2-byte floating point
value
Data type
Switching
Switching
Switching
│76