Basic Stage Cooling; Basic Stage Cooling - Status Object Cooling; Basic Stage Cooling - Mode Of The Control Value - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

This parameter enables additional functions and communication objects, e.g. "Basic stage
cooling".

10.1.40 Basic stage cooling

Note
Only available when the "Extended settings" parameter under "Cooling control"
is set on "Yes".

10.1.41 Basic stage cooling - Status object cooling

Options:
This parameter enables the "Status cooling" communication object.

10.1.42 Basic stage cooling - Mode of the control value

Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
Normal: Value 0 means "Valve closed".
Inverse: Value 0 means "Valve open".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Yes
No
Yes
Normal
Inverse
Application "RTC object"
│45