Typical values for summer compensation are:
21°C: Lower outside temperature value
32°C: Upper outside temperature value
0 K: Lower setpoint offset
6 K: Upper setpoint offset
This means that a continuous increase of the minimum setpoint value for cooling occurs to a
value equal to the outside temperature minus a setpoint offset of 0 to 6 K if the outside
temperature increases to 32°C from 21°C.
For example:
For an increasing outside temperature, the minimum setpoint value for cooling will be increased
starting at an outside temperature of 21°C. The minimum setpoint temperature for cooling is
25.1°C at an outside temperature of 30°C; 25.5°C at an outside temperature of 31°C; 26°C at
an outside temperature of 32°C; and 27°C at an outside temperature of 33°C.
10.1.124 Summer compensation - (Lower) Starting temperature for summer compensation (°C)
Options:
The parameter defines the lower outside temperature value up to which temperature value the
setpoint correction (summer compensation) is performed based on too high an outside
temperature.
Note
This parameter is only available if the "Summer compensation" parameter is set
to "Yes".
10.1.125 Summer compensation - Offset of the set-point temperature for the entry into summer
compensation (x 0.1°C)
Options:
The parameter is used to define how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the lower temperature value is reached.
Typical values for summer compensation are:
20°C: Lower outside temperature value
32°C: Upper outside temperature value
0 K: Lower setpoint offset
4 K: Upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Note
This parameter is only available if the "Summer compensation" parameter is set
to "Yes".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Setting option between -127 - 127
Setting option between -127 - 127