General - Operating Mode After Reset - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

Heating and cooling: For operating a two-wire or four-wire system used to heat or cool a
room. Switching between heating and cooling takes place using a central switch (two-wire
system) or is carried out manually and / or automatically via the single room temperature
controller (four-wire system).
Heating and cooling with an additional stage: In addition to the heating and cooling
functions, one additional stage each with an autonomous controller type can be
programmed.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
10.1.3

General - Operating mode after reset

Options:
After a reset the device will run in the operating mode after a restart until a new operating mode
is set as the result of device operation or by communication objects, as the case may be. This
operating mode should be defined during the planning phase. An improperly defined operating
mode can result in a loss of comfort or increased energy consumption.
Comfort: If the room temperature is not automatically lowered and the room is therefore
controlled independent of its use.
Standby: If the room is controlled automatically, e.g. by a presence detector, as a function of
its use.
Eco mode: If the room is controlled automatically or manually as a function of it use.
Frost/heat protection: If only the building protection function is necessary in the room after a
reset.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Comfort
Standby
Eco mode
Cooling with additional stage
Frost/heat protection
Application "RTC object"
│31