117 Fan Coil Settings For Heating - Maximum Speed Level Heating For Eco Mode; 118 Fan Coil Settings For Cooling; 119 Fan Coil Settings For Cooling - Speed Level 1 To 5 Up To Control Value (0 To 255) Cooling; 120 Fan Coil Settings For Cooling - Fan Speed Level Limit Cooling For Eco Mode - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

10.1.117 Fan coil settings for heating - Maximum speed level heating for eco mode

Options:
Specifies the maximum possible fan speed level when the system is switched to eco mode.

10.1.118 Fan coil settings for cooling

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device" and the "Control value type" parameter
is set on "Fan coil". In addition, the "Control function" parameter must be set on
either "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".

10.1.119 Fan coil settings for cooling - Speed level 1 to 5 up to control value (0 to 255) cooling

Options:
In this parameter, the control values of the controller are assigned to fan speed levels. This
assignment is used if the fan speed levels are transmitted together with the control values.
Note

10.1.120 Fan coil settings for cooling - Fan speed level limit cooling for eco mode

Options:
This parameter limits the fan speed level when the system is switched to eco mode.

10.1.121 Fan coil settings for cooling - Maximum fan speed level cooling for eco mode

Options:
Specifies the maximum possible fan speed level when the system is switched to eco mode.
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Setting option between 0 - 5
Setting option between 0 - 255
These level settings should be adjusted to match the settings in the fan coil
actuator.
Setting the "Control value type" to "Fan coil" in the control parameters is only
useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the
control of only one fan coil actuator each for heating and cooling is
supported.
The "Fan speed level 4 - 5 up to control value (0 - 255) cooling" parameters
are available only when the "Number of fan speed levels" is set on "5 levels".
No
Yes
Setting option between 0 - 5
Application "RTC object"
│67