Setpoint Adjustment - Maximum Manual Reduction During Cooling Mode (0 - 15°C); Setpoint Adjustment - Resetting Of The Manual Adjustment For Receipt Of A Basic Setpoint - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

Options:
This preset can be used to limit the manual increase during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
10.1.87 Setpoint adjustment — Maximum manual reduction during cooling mode (0 - 15°C)
Options:
This preset can be used to limit the manual decrease during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".

10.1.88 Setpoint adjustment - Resetting of the manual adjustment for receipt of a basic setpoint

Options:
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Setting option between 0 - 15
Setting option between 0 - 15
No
Yes
Application "RTC object"