Setpoint Settings - Hysteresis For Switchover Heating/Cooling (X 0.1°C); Setpoint Settings - Setpoint Temperature For Heating And Cooling Comfort (°C); Setpoint Settings - Setpoint Temperature For Heating Comfort (°C); Setpoint Settings - Reduction For Standby Heating (°C) - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

10.1.69 Setpoint settings - Hysteresis for switchover heating/cooling (x 0.1°C)
Options:
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling. If the
room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating.
Note
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
10.1.70 Setpoint settings - Setpoint temperature for heating and cooling comfort (°C)
Options:
Specifies the comfort temperature for heating and cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
10.1.71 Setpoint settings - Setpoint temperature for heating comfort (°C)
Options:
Specifies the comfort temperature for heating when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating" or "Heating with additional stage".
10.1.72 Setpoint settings - Reduction for standby heating (°C)
Options:
Specifies the temperature in heating mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Setting option between 5 - 100
Setting option between 10 - 40
Setting option between 10 - 40
Setting option between 10 - 40
Application "RTC object"
│55

Advertisement

Table of Contents
loading

Table of Contents