10.1.32 Additional heating stage - Cyclic sending of the control value (min)

Options:
The current control value used by the device can be cyclically transmitted to the bus.
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On", "2-point 1 Byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".
Additional heating stage - Maximum control value (0 - 255)
Options:
The maximum control value of the PI controller defines the maximum value outputted by the
controller. If a maximum value under 255 is chosen, the value will not be exceeded, even if the
controller calculates a higher control value.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".

10.1.33 Additional heating stage - Minimum control value for basic load (0 - 255)

Options:
The minimum control value of the PI controller defines the minimum value output by the
controller. If a minimum value greater than zero is chosen, the controller will not output a lower
value, even if it calculates a value that is lower. This parameter can be used to set a basic load,
e.g. for operating floor heating. Even if the controller calculates the control value zero, a heating
medium will flow through the floor heating system to prevent the floor from cooling down. Under
"Settings of basic load", it is also possible to define whether this basic load will be permanently
active or whether it will be switched by the "Basic load" object.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Setting option between 1 - 60 minutes
Setting option between 0 - 255
Setting option between 0 - 255