10.3.10 Current setpoint

Number
11
The object outputs the current setpoint temperature resulting from the following: the
parameterized setpoint temperature of the current operation type and operating mode, the
manual setpoint temperature adjustment, a change in the base setpoint temperature via the
base setpoint value object. This is purely a transmitting object.

10.3.11 Operating mode

Number
12
The "Operating mode" object receives, as a 1-byte value, the operating mode that is to be set.
Here value 1 means "Comfort", value 2 "Standby", value 3 "Economy" and value 4 "Frost/heat
protection".
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller can also be defined by objects "Superimposed operating
mode", "Condensate ware alarm", "Dew alarm", "Window contact", "Control On/Off", "Presence
detector" and "Operating mode (listed in decreasing order of priority).
Note
Item 2:
If the master/slave mode is the active operating mode, the Operating mode
(slave) object must be connected to this object.
Item 3:
If the master/slave mode is the active operating mode, the operating mode
(master) object must be connected to this object.
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Name
Current setpoint
Name
1. Operating mode
2. Operating mode (master)
3. Operating mode (slave)
Communication objects - RTC
Object function
Output
Object function
Input / output
Input / output
Input / output
Data type
2-byte floating point
value
Data type
HVAC mode
HVAC mode
HVAC mode
│77