Additional Cooling Stage; Additional Cooling Stage - Mode Of The Control Value; Additional Cooling Stage - Hysteresis (X 0.1°C) - ABB i-bus 6108/18-BS-500 Technical Reference Manual

Knx room temperature controller with display
Table of Contents

Advertisement

This parameter enables additional functions and communication objects, e.g. "Additional cooling
stage".

10.1.53 Additional cooling stage

Note
Only available when the "Extended settings" parameter under "Control of
additional cooling stage" is set on "Yes".

10.1.54 Additional cooling stage - Mode of the control value

Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
Normal: Value 0 means "Valve closed".
Inverse: Value 0 means "Valve open".
10.1.55 Additional cooling stage - Hysteresis (x 0.1°C)
Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
KNX Technical Reference Manual 1473-1-8914 / 2CKA001473B8914
Description of application and parameters
Yes
Normal
Inverse
Setting option between 3 - 255
Application "RTC object"
│50