Fan Coil Settings Heating; Fan Coil Settings For Heating - Speed Level 1 To 5 Up To Control Value (0 To 255) Heating; Fan Coil Settings For Heating - Fan Speed Level Limit Heating For Eco Mode; Fan Coil Settings For Heating - Maximum Speed Level Heating For Eco Mode - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.124 Fan coil settings heating

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device" and the "Control value type" parameter
is set on "Fan coil". In addition, the "Control function" parameter must be set on
either "Heating", "Heating with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
11.5.125 Fan coil settings for heating — Speed level 1 to 5 up to control value (0 to 255) heating
Options:
In this parameter, the control values of the controller are assigned to fan speed levels. This
assignment is used if the fan speed levels are transmitted together with the control values.
Note
11.5.126 Fan coil settings for heating — Fan speed level limit heating for eco mode
Options:
This parameter limits the fan speed level when the system is switched to eco mode.

11.5.127 Fan coil settings for heating - Maximum speed level heating for eco mode

Options:
Specifies the maximum possible fan speed level when the system is switched to eco mode.
Note
The parameter is only adjustable if the "Fan speed level limit heating in Eco
mode" parameter is set on "Yes".
Product manual 2CKA001473B9482
Description of application and parameters
Setting option between 0 - 255
These level settings should be adjusted to match the settings in the fan coil
actuator.
Setting the "Control value type" to "Fan coil" in the control parameters is only
useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the
control of only one fan coil actuator each for heating and cooling is
supported.
The "Fan speed level 4 - 5 up to control value (0 - 255) heating" parameters
are available only when the "Number of fan speed levels" is set on "5 levels".
No
Yes
Setting option between 0 - 5
Application "Function block RTC"
│121