Selector E makes it possible to configure the supply voltage of the device in a 115/230 V AC version.
Energize the device with a
230 V AC voltage.
Figure 12:
Selector of the supply voltage on a 115/230 V AC version
Loosen the nuts of the cable glands.
Insert each cable through a nut than through the cable gland, using the cable glands as shown in "Figure 13".
Flow sensor cable
Figure 13:
Using the cable glands
Remove the two terminal blocks (marked 6 and 7 in "Figure 10") from the housing.
Figure 14:
Inserting the cable clips
Depending on the operating voltage of the device, wire according to chap. "7.4.5" to "7.4.10".
Insert the two terminal blocks (marked 6 and 7 in "Figure 10") into their original position.
Letting the housing stay completely open, secure the power supply cable, the flow sensor connection cable
and, depending on the version, the relay connection cables, with the cable clips.
Tighten the cable glands making sure the cable in the housing is long enough to allow complete opening of
the housing.
Close the cover.
Fully screw the 4 screws.
Put the blanking strips on the housing.
22
Cables of the outputs
Before wiring the device insert the supplied cable clips into the slots of
the electronic board and of the 115/230 V AC power supply board if
the device has such a board.
English
E
Energize the device with a
115 V AC voltage.
Power supply cable
12-36 V DC or 115/230 V AC
Type 8025 UNIVERSAL
Installationandwiring