Specifications Of The Connected Flow Sensor; Electrical Connection - Burkert 8025 Series Operating Instructions Manual

Universal flow transmitter
Hide thumbs Also See for 8025 Series:
Table of Contents

Advertisement

Available languages

Available languages

Type 8025 UNIVERSAL
Technicaldata
6.3.3

Specifications of the connected flow sensor

Signal originating from the remote sensor
• type
• frequency
• max. voltage
Input impedance
Power supply
6.3.4

Electrical connection

Type of connection
Cable specifications
• cable type
• Cross section of wires
• Diameter of each cable (for the cable glands
M16x1,5 of the wall-mounted version)
• pulse, sine-wave (typical sensitivity 50 mV peak-
to-peak at 250 Hz), "on/off", or standard voltage
0-5 V DC
• 0,6 Hz to 2,2 kHz, can be adjusted
• 36 V DC
depends on the position of selector "LOAD" on the
electronic board of the 8025. See chap. "7.4.10"
supplied by the transmitter depending on the position
of selector "SENSOR SUPPLY" of the 8025, either:
• 5 V DC, 30 mA max.
• (L+)-12V: supply voltage (L+) of the transmitter
minus 12 V DC (minus 12,5 V DC max.), 80 mA max.
• L+: supply voltage (L+) of the transmitter (minus
1,5 V DC max.), 140 mA max. (if the device is ener-
gized with 12-36 V DC), 80 mA max. (if the device is
energized with 115/230 V AC)
on the terminal blocks of the electronics (and through
cable glands M16x1,5, for the wall-mounted versions)
• shielded
• 0.2 to 1.5 mm
2
• 4 to 8 mm
English
13