Type 8025 UNIVERSAL
Maintenanceandtroubleshooting
9.3.3
Resolution of problems without message generation and
with device status LED orange
Device
current
status leD
output
Ao1
orange
4-20 mA Switched
orange
4-20 mA Switched
orange
4-20 mA Switched
orange
4-20 mA Switched
orange
4-20 mA Switched
If the output is configured to switch when a warning message is generated. See chap. 8.6.5.
2)
output Do1
message
and/or Do2
displayed
and/or Do3
"WARN.
2)
LO"
"WARN.
2)
HI"
"DISP.
2)
OVF"
"AO1
2)
LOST"
"WARN.
2)
VOL."
possible cause
The measured flow rate
has stayed under the
minimum threshold for
the set time delay.
This message appears
when the flow rate
is monitored (see
chap. 8.7.4).
The measured flow rate
has stayed above the
maximum threshold for
the set time delay.
This message appears
when the flow rate
is monitored (see
chap. 8.7.4).
The real flow rate cannot
be displayed (display has
reached its max. possible
value).
Except the display,
the device operates
depending on the real
flow rate.
Calibration of the current
output is lost.
The device generates
unprecise intensities
on the analogue output
AO1.
The daily totalizer has
reached the value set in
parameter "VOLUME-
W." of the Test menu.
recommended action
Check the flow rate in the
pipe and its consequences
on the process.
If necessary, clean the flow
sensor.
Check the flow rate in the
pipe and its consequences
on the process.
If necessary, clean the flow
sensor.
Adjust the unit or the number
of decimals in the UNIT
parameter of the Parameters
menu so that the display can
show higher values.
Adjust the current output
within the Test menu.
Carry out the planned main-
tenance operation.
Reset the daily totalizer: see
chap. "8.5" or "8.6.15".
English
61

Advertisement

Chapters

Table of Contents
loading

Table of Contents