Table 20. AI1 Settings—P2.4
Code
Parameter
P2.4.1
AI1 Mode
P2.4.2
AI1 Signal Range
2
P2.4.3
AI1 Custom Min
2
P2.4.4
2
AI1 Custom Max
P2.4.5
AI1 Filter Time
2
P2.4.6
2
AI1 Signal Invert
Table 21. AI2 Settings—P2.5
Code
Parameter
P2.5.1
AI2 Mode
P2.5.2
AI2 Signal Range
2
P2.5.3
AI2 Custom Min
2
P2.5.4
2
AI2 Custom Max
P2.5.5
AI2 Filter Time
2
P2.5.6
2
AI2 Signal Invert
Table 22. Digital Output—P3.1
Code
Parameter
P3.1.1
2
DO1 Function
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Min.
Max.
0.00
See Par ID 177
See Par ID 176
100.00
0.00
10.00
Min.
Max.
0.00
See Par ID 185
See Par ID 184
100.00
0.00
10.00
Min.
Max.
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Unit
Default
1
0
%
0.00
%
100.00
s
0.10
0
Unit
Default
0
1
%
0.00
%
100.00
s
0.10
0
Unit
Default
1
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Step 5—Standard Parameter List
ID
Note
222
0 = 0–20 mA
1 = 0–10 V
175
0 = 0–100%/0–20 mA/0–10 V
1 = 20–100%/4–20 mA/2–10 V
2 = Customized
176
177
174
181
0 = Not Inverted
1 = Inverted
ID
Note
223
0 = 0–20 mA
1 = 0–10 V
2 = -10– +10 V
183
0 = 0–100%/0–20 mA/
0 =
0–10 V/-10–10 V
1 = 20–100%/4–20 mA/
1 =
2–10 V/-6–10 V
2 = Customized
184
185
182
189
See Par ID 181
ID
Note
151
0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
13 = OverHeat Fault
14 = OverCurrent Regular
15 = OverVoltage Regular
16 = UnderVoltage Regular
17 = 4mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
23 =
Direction
24 = Thermistor Fault Output
21